Remeha Tzerra Ace

Control and adjustment of combustion

Switch on at full load


Press the R and - keys at the same time to select the chimney sweep mode.

The device is now running at low load. wait a moment until L appears in the display.

Press the key twice

The device is now running at full load. Wait a moment until H appears in the display.

Control/set valuesO2 Full load


Tzerra Ace

O2 (%) 3.5 - 4.0

Follow these steps:

    Set the boiler to full load. Measure the percentage of O2. Compare the measured values with those below.

Turn screw A counterclockwise for a lower percentage.

Adjust to full load

See drawing for the position of the adjustment screw A for full load.


Control/set valuesO2 Low load


Tzerra Ace

O2 (%) 4,7 - 5,2

Follow these steps:

    Set the boiler to low load. Measure the percentage of O2. Compare the measured values with those below.

Turn screw B counterclockwise for a lower percentage.

Adjust to Low load

See drawing for the position of the adjustment screw B for Low load.